2.2.14. Sanitation


                       2.2.14.1. Urinals

                  • A urinal should not be set closer than 450mm

                  from its center to any side wall partition, vanity,
                        Thesis Report V-SPARC VIT
                  or  other  obstruction,  or  closer  than  900mm
                  center-to-center between adjacent fixtures.
                  • There should be at least 900mm of clearance in

                  front of the urinal to any wall, fixture, or door.

                  •  Individual  wall-hung  urinal  units  shall  be  at
                  least 300mm wide, and the lip of the collection

                  area  shall  project  from  the  wall  by  at  least

                  300mm.
                  •  To  provide  a  visual  barrier  between  urinals,

                  modesty boards of at least 300 mm by 1800 mm
                  (Height) should be placed between them.

                                                                           Figure 2 Sanitary requirement in public building
                  2.2.14.2. Wash Basins


                       Wash basins should be substantial in size.

                       The basins should have a minimum size of 500mm in length and 400mm in width
                  2.2.14.3. Water Closets:


                  •      A  WC  should  not  be  set  closer than  450mm  from  its  centre to  any  side  wall,
                  partition, vanity or other obstruction.

              •  There should be at least a 900mm clearance in front of the WC to any wall, fixture or door.
              •  Supply a predetermined quantity of not more than 4.5 litres of water per flush after each

                  use.