Any changes in travel direction in ramp shall be preceded by
landings of 1.5 m × 1.5 m size.
Every landing shall be not less than 1500 mm long in the direction
of travel.
2.2.7. Ceiling Height
Thesis Report V-SPARC VIT
Every assembly room, gymnasium shall have a clear height of 3.6m
except under a girder which may project 0.6m below the required ceiling
height.
A clear internal height under balcony or a girder shall not be less
than 3.0m.
A minimum room height for classroom in all schools and other
institutions shall not be less than 3.0m.
The minimum head room under beams shall be 2.75m.
2.3. Area Required
2.3.1. Teaching Hospital
Carpet Area = 66 m² per bed
= 66 m² x 500
= 33,000 m²
Built-up area = Carpet area + 10% of carpet area*
= 33,000 + 10% of 33,000
= 33,000 + 3,300 m²
= 36,300 m²
*10% consideration for built up area is for the walls
2.3.2. Nursing College
Built-up for Nursing College = 3% of the total site area
= 3% of 55.3 acres